Underground Service Entrance Cable. 600 Volt. Copper Conductors. Cross-Linked Polyethylene
(XLP) Insulation. High-Heat, Moisture, and Sunlight Resistant. Sizes 6 Through 4/0 AWG Also
Rated SIS.
Southwire® Type RHH or RHW-2 or USE-2 conductors are used with conduit as
specified in the 2011 National Electrical Code. When used as Type USE-2, conductor
is suitable for use as underground service entrance cable for direct burial at conductor
temperatures not to exceed 90° C. When used as RHH, conductor temperatures shall
not exceed 90°C in dry locations. When used as RHW-2 or USE-2, conductor
temperatures shall not exceed 90°C in wet or dry locations. Voltage rating for RHH or
RHW-2 or USE-2 conductors is 600 volts.
Southwire® Type RHH or RHW-2 or USE-2 comply with the following:
• ASTM - B3, B8 (7, 19, 37, 61 Strands), B787 (19 Wire Combination Unilay Strand)
• UL Standard 44 for RHH or RHW-2
• UL Standard 854 for USE-2
• Federal Specification A-A-59544
• National Electrical Code, NFPA 70 - 2011 Edition
• NEMA WC 70 Construction Requirements
• RoHS/REACH Compliant
Southwire® Type RHH or RHW-2 or USE-2 copper conductors are annealed (soft)
copper. Insulation is an abrasion, moisture, heat, and sunlight resistant black crosslinked polyethylene (XLP). An optional CT rated product is available upon request for
sizes 1/0 and larger.
Copper RHH, RHW-2, USE-2
APPLICATIONS
STANDARDS & REFERENCES
CONSTRUCTION
RECOMMENDED SAMPLE SPECIFICATIONS:
Conductors shall be UL-listed Tpe RHH or RHW-2 or USE-2, suitable for operation at 600 volts or less in wet or dry locations, including direct
burial in the earth. Conductors shall be annealed copper, cross-linked polyethylene (XLP) insulated, as manufactured by Southwire Company
or approved equal.
Size (AWG
or kcmil)
No. of strands 60°C 75°C 90°C
14 7 45 160 20 15 15 15 AC
12 7 45 177 29 20 20 20 AC
10 7 45 201 42 30 30 30 AC
8 7 60 256 68 40 50 55 AC
6 7 60 294 101 55 65 75 ABCD
4 7 60 341 154 70 85 95 ABCD
2 7 60 397 235 95 115 130 ABCD
1 19 80 484 309 110 130 145 B
1/0 19 80 520 379 125 150 170 ABC
2/0 19 80 557 472 145 175 195 ABC
3/0 19 80 614 583 165 200 225 ABC
4/0 19 80 673 729 195 230 260 BC
250 37 95 748 863 215 255 290 BC
300 37 95 804 1029 240 285 320 AB
350 37 95 854 1191 260 310 350 AB
400 37 95 899 1352 280 335 380 A
500 37 95 983 1674 320 380 430 AB
600 61 110 1089 2012 350 420 475 A
700 61 110 1158 2332 385 460 520 N/A
750 61 110 1191 2492 400 475 535 C
800 61 110 1223 2642 410 490 555 N/A
900 61 110 1283 2970 435 520 585 N/A
1000 61 110 1340 3288 455 545 615 C
Package
Codes:
A-2,500'
B-1,000'
C-500'
D-5,000'
+ Allowable ampacities shown are for general use as specified by the National Electrical Code, 2011
Edition, section 310.15 and 240.4(D)
Unless the equipment is marked for use at higher temperatures the conductor ampacities shall be limited to the
following per NEC 110.14(C)
60º C- When terminated to equipment for circuits rated 100 amperes or less or marked for 14- 1 AWG conductors.
75º C- When terminated to equipment for circuits rated over 100 amperes or marked for 1/0 AWG or larger
conductors.
90º C- Wet or dry locations for ampacity adjustment purposes using NEC section 310.15
Standard
Package
Conductor
Insulation
Thickness
(mils)
Nominal
O.D.
(mils)
Approx.
Net Wt.
Per
1000'
(lbs.)
Allowable Ampacities+
Size
(AWG
or kcmil)
No. of strands Stock Numbers
14 7 Stock #: BK:890700
12 7 Stock #: BK:113431, GN:678573
10 7
Stock #: BK:113449, WE:563196,
RD:890146, GN:953539
8 7
Stock #: BK:113456, WE:643957,
RD:952689, BE:588683, GN:655993
6 7
Stock #: BK:113464 WE:640110,
RD:952671, BE:959726, GN:640128
4 7
Stock #: BK:113472, WE:476565,
RD:476549, BE:643577, GN:952663, OE:588746
2 7
Stock #: BK:113498, WE:476523,
RD:476531, BE:643544, GN:958009
1 19 Stock #: BK:113506
1/0 19 Stock #: BK:113514, WE:643973
2/0 19 Stock #: BK:113522, GN:591255
3/0 19 Stock #: BK:113530
4/0 19 Stock #: BK:113548, GN:587561
250 37 Stock #: BK:113555
300 37 Stock #: BK:113563
350 37 Stock #: BK:113571
400 37 Stock #: BK:113589
500 37
Stock #: BK:113597, BN:580165,
OE:580166, YW:580168, GY:580169
600 61 Stock #: BK:113605
700 61 Stock #: N/A
750 61 Stock #: BK:113613
800 61 Stock #: N/A
900 61 Stock #: N/A
1000 61 Stock #: BK:113647
Color Abbreviations
BK-Black BN-Brown OE-Orange YW-Yellow GY-Grey
WE-White RD-Red BE-Blue GN-Green
Conductor

PDF Document reader online

This website is focused on providing document in readable format, online without need to install any type of software on your computer. If you are using thin client, or are not allowed to install document reader of particular type, this application may come in hand for you. Simply upload your document, and Docureader.top will transform it into readable format in a few seconds. Why choose Docureader.top?

  1. Unlimited sharing - you can upload document of any size. If we are able to convert it into readable format, you have it here - saved for later or immediate reading
  2. Cross-platform - no compromised when reading your document. We support most of modern browers without the need of installing any of external plugins. If your device can oper a browser - then you can read any document on it
  3. Simple uploading - no need to register. Just enter your email, title of document and select the file, we do the rest. Once the document is ready for you, you will receive automatic email from us.

Previous 10

Next 10