BEFORE BEGINNING ANY MODIFICATION, BE SURE THE
MAIN DISCONNECT SWITCH IS IN THE “OFF” POSITION.
TAG DISCONNECT WITH A SUITABLE WARNING LABEL.
INSTALLATION PROCEDURE
CAUTION:When making threaded connections, use a backup wrench to avoid breaking brazed connection.
1. Remove covers required to gain access to the control box
and the compressor area.
2. Locate and remove access cap from Schrader port on the
liquid line (tube).
3. Attach high pressure control to Schrader port as shown in
Figure 1.
ELECTRICAL CONNECTIONS
NOTE: In some instances, it may be necessary to clip the
quick-connect terminals from wire leads and strip the insulation from the end of the leads to make the electrical connections. Wire nuts have been provided for that purpose.
1. Locate unit contactor coil terminals on contactor in unit
control box. The yellow and brown leads are located in the
low voltage cover of the control box and connection may
be made to the yellow lead.
2. Make electrical connection as follows (Refer to wiring diagram with unit.)
a. Locate, break and strip the ends of the yellow lead,
between the contactor coil and the low voltage cover.
Attach one pressure control lead to the stripped end of
yellow contactor coil lead using a wire nut. Attach the
other pressure control lead to the yellow wire in the low
voltage cover using the other wire nut.
b. Reinstall access panels.
c. Restore power to the unit and check unit operation.
INSTALLATION INSTRUCTIONS
HIGH PRESSURE CONTROL KIT - R410A
RXAB-A08 REMOTE CONDENSING UNITS
11⁄2 THROUGH 5 TON UNITS
92-21458-68-00
THIS ACCESSORY IS INTENDED TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO AVOID
UNSATISFACTORY OPERATION OR DAMAGE TO THE PRODUCT AND POSSIBLE UNSAFE CONDITIONS, INCLUD-
ING ELECTRICAL SHOCK, REFRIGERANT LEAKAGE AND FIRE, THE INSTALLATION INSTRUCTIONS PROVIDED
WITH THIS ACCESSORY MUST BE STRICTLY FOLLOWED AND THE PARTS SUPPLIED USED WITHOUT SUBSTITU-
TION. DAMAGE TO THE PRODUCT RESULTING FROM NOT FOLLOWING THE INSTRUCTIONS OR USING UNAUTHO-
RIZED PARTS MAY EXCLUDED FROM THE MANUFACTURER’S PRODUCT WARRANTY COVERAGE.
WARNING!
Recognize this symbol as an indication of Important Safety Information!!
PARTS LIST
DESCRIPTION PART NUMBER QTY.
High Pressure Control 47-102290-01 1
Wire Nuts 45-18058-01 2
Instructions 92-21458-68 1
WARNING!
FIGURE 2
WIRING
FIGURE 1
HIGH PRESSURE CONTROL INSTALLED

PDF Document reader online

This website is focused on providing document in readable format, online without need to install any type of software on your computer. If you are using thin client, or are not allowed to install document reader of particular type, this application may come in hand for you. Simply upload your document, and Docureader.top will transform it into readable format in a few seconds. Why choose Docureader.top?

  1. Unlimited sharing - you can upload document of any size. If we are able to convert it into readable format, you have it here - saved for later or immediate reading
  2. Cross-platform - no compromised when reading your document. We support most of modern browers without the need of installing any of external plugins. If your device can oper a browser - then you can read any document on it
  3. Simple uploading - no need to register. Just enter your email, title of document and select the file, we do the rest. Once the document is ready for you, you will receive automatic email from us.

Previous 10

Next 10