Guide for installers
METTLER TOLEDO MultiRange
Explosion proof weighing system
with IND226x weighing terminal
RS422
CL20mA
RS232
ACM200
Hazardous area Safe area
www.mt.com/support
Contents
Guide for installers 72203958C 11/12 3
IND226x
Contents Page
1 Safety instructions....................................................................... 4
2 System overview ......................................................................... 6
2.1 Typical configurations ................................................................... 6
2.2 Description of components ............................................................ 8
3 Installation.................................................................................. 10
3.1 Setting up system modules ............................................................ 10
3.2 Connecting devices ....................................................................... 11
3.3 Selecting peripheral devices ........................................................... 13
3.4 Installing the equipotential bonding................................................. 14
3.5 Connecting power supply .............................................................. 14
4 Optional work.............................................................................. 15
4.1 Customizing connection cables: Weighing platform / APS768x .......... 15
4.2 Connection cable extension power supply unit APS500 / APS501 ...... 16
4.3 Customizing connection cables: Second display /
interface converter ACM200 ........................................................... 18
4.4 Configuring module ACM200-CL/RS422 ......................................... 19
5 Technical data............................................................................. 20
5.1 Dimensional drawing .................................................................... 20
5.2 Technical data of the CL20mA interface of the module
ACM200-CL/RS422 ...................................................................... 21
6 Disposal ..................................................................................... 22
7 Terminal diagram ........................................................................ 24
Safety instructions IND226x1 Safety instructions
The IND226x weighing terminal is approved for operation in Zone 1 and 21
hazardous areas as well as for Division 1 areas. The interface converter ACM200
may only be installed and operated in the safe area.
If the IND226x weighing terminal is used in hazardous areas, special care must be
taken. The code of practice is oriented to the "Safe Distribution" concept drawn up by
METTLER TOLEDO.
Competence ▲ The weighing system may only be installed, maintained and repaired by
authorized METTLER TOLEDO service personnel.
▲ The mains supply may only be installed by a specialist authorised by the owneroperator.
Ex approval ▲ No modifications may be made to the terminal and no repair work may be
performed on the modules. Any weighing platform or system modules that are
used must comply with the specifications contained in the installation
instructions. Non-compliant equipment jeopardizes the intrinsic safety of the
system, cancels the "Ex" approval and renders any warranty or product liability
claims null and void.
▲ The safety of the weighing system is only guaranteed when the weighing system
is operated, installed and maintained in accordance with the respective instructions.
▲ Also comply with the following:
– the instructions for the system modules,
– the regulations and standards in the respective country,
– the statutory requirement for electrical equipment installed in hazardous areas
in the respective country,
– all instructions related to safety issued by the owner.
▲ The explosion-protected weighing system must be checked to ensure compliance
with the requirements for safety before being put into service for the first time,
following any service work and every 3 years, at least.
Operation ▲ Prevent the build-up of static electricity. Always wear suitable working clothes
when operating or performing service work in a hazardous area.
▲ Do not use protective coverings for the devices.
▲ Protect the keyboard membrane against ultraviolet radiation.
▲ Avoid damage to the system components.4 Guide for installers 72203958C 11/12
Safety instructionsIND226xInstallation ▲ Only install or perform maintenance work on the weighing system in the
hazardous areas if the following conditions are fulfilled:
– if the intrinsically safe characteristic values and zone approval of the individual
components are in accord with one another,
– the owner has issued a permit ("spark permit" or "fire permit"),
– the area has been rendered safe and the owner's safety co-ordinator has
confirmed 11/12 there is no danger,
– the necessary tools and any required protective clothing are provided (danger
of the build-up of static electricity).
▲ The certification papers (certificates, manufacturer’s declarations) must be present.
▲ Lay cabling securely so that it does not move and effectively protect it against
damage.
▲ Only route cables into the housing of the system modules via the approved
earthing cable glands and ensure proper seating of the seals.Guide for installers 72203958C 11/12 5
System overview IND226x2 System overview
2.1 Typical configurations
A weighing system with the IND226x weighing terminal can be operated either with
one of the following power supply units or with an external storage battery:
APS500 Power supply unit in a hazardous area,
US version, 120 VAC, 50/60 Hz
APS501 Power supply unit in a hazardous area,
EU version, 240 VAC, 50/60 Hz
APS768x-120 V Power supply unit in a hazardous area,
US version, 120 VAC, 50/60 Hz
APS768x-230 V Power supply unit in a hazardous area,
EU version, 230 VAC, 50 Hz
External NiMH Battery Pack External storage battery for a hazardous area,
charging only in a non-hazardous area and using a
charger specified and approved by METTLER
TOLEDO
Either an analog weighing platform or the system solution Analog Ex1 can be
connected to the weighing IND226x terminal.
The following components are necessary for connection of peripheral devices:
Interface IND Active intrinsically safe data interface,
installed in IND226x (Master)
Interface Remote Passive intrinsically safe data interface, for remote
control of an IND226x (IND226x as a second
display), installed in IND226x (second display)
ACM200 Interface converter for the safe area,
for example, for connection of a PC in the safe area
Wide range power supply unit 100 – 240 V AC,
50/60 Hz or 24 V DC6 Guide for installers 72203958C 11/12
System overviewIND226x2.1.1 Configuration with interface converter ACM200 in the safe area
IND226x
APS50. Ex-i
max. 15 m
APS768x Ex-i
max. 50 m
Battery
Pack
Ex-i
max. 3 m
Analog weighing
platform
Wc System
solution
Analog Ex1
Wc Wc Wc Ex-i
max. 122 m
Ex-i
max. 122 m
Hazardous area Safe area
Ex-i
max.
300 m
Interface
IND ACM200
RS422/
CL20mA
RS232 *
RS422/485 *
alternative
CL20mA *
alternative
* only one hardware interface available,
CL20mA and RS422/485 only with module ACM200-CL/RS422
Dashed-line components are alternatives.
2.1.2 Configuration with remote controlled IND226x (second display)
IND226x
(Master)
Analog
Wheiging platform
Ex-i
max. 122 m
Interface
IND
IND226x
(Second display)
APS50.
Ex-i
max. 15 m
Interface
Remote
E
x-i m
ax. 300 m
Battery
Pack
Ex-i
max. 3 m
APS768x Ex-i
max. 50 m
Wc System solution
Analog Ex1
Wc Wc Wc Ex-i
max. 122 m
APS50.
Ex-i
max. 15 m
Battery
Pack
Ex-i
max. 3 m
APS768x Ex-i
max. 50 m
Hazardous area Safe area
Dashed-line components are alternatives.Guide for installers 72203958C 11/12 7
System overview IND226x2.1.3 Configuration with interface converter ACM200 and power supply unit APS768x
* IDNet version
2.2 Description of components
2.2.1 Approvals
IND226x weighing
terminal
Interface IND
Interface Remote
Ignition protection type EN / IEC Ex II 2G Ex ib IIC T4 Gb, –10 °C ... +40 °C
II 2D Ex ib IIIC T60°C Db
CFMUS IS Class I, II, III; Division 1;
Group A, B, C, D, E, F, G; T4; Ta = 40 °C
Power supply unit
APS500 / APS501
See documentation on APS500 / APS501
Power supply unit
APS768x
See APS768x Guide for installers
External Battery Pack See documentation on External NiMH Battery Pack
Analog weighing
platforms
See Operating instructions / Installation information of the weighing platforms
System solution
Analog Ex1
See Guide for installers of the System solution Analog Ex1
Interface converter
ACM200
Ignition protection type EN / IEC Ex II (2)G [Ex ib Gb] IIC
II (2)D [Ex ib Db] IIIC
CFMUS AIS Class I, II, III; Division 1;
Group A, B, C, D, E, F, G
max. 100 m
max.
300 m
K...x-T4,
WMH...Ex
PFA57.x*,
PTA459x*,
PUA579x*
ACM200
Interface
CL/RS
CL
IDNet
RS
or IND...
PC
Interface
CL/CL8 Guide for installers 72203958C 11/12
System overviewIND226x2.2.2 Connections
1 2 3 4
1 Weighing platform connection;
earthing cable gland M16x1.5 included in supply
2 Connection of interface converter ACM200 or digital input;
blind plugs mounted at the factory
3 Connection of power supply unit / External Battery Pack;
earthing cable gland M16x1.5 included in supply
4 Equipotential bonding terminal (EB)Guide for installers 72203958C 11/12 9
Installation IND226x3 Installation
EXPLOSION HAZARD
The explosion-protected weighing system may only be installed according to these
installation instructions and the terminal diagram 72203677 on Pages 24 to 29.
3.1 Setting up system modules
3.1.1 Setting up the IND226x weighing terminal
➜ Select a suitable installation site.
Bench stand or floor stand mounting
➜ Place weighing terminal onto the bench or floor stand and mount with 4 screws.
Wall mounting
➜ The IND226x weighing terminal can be mounted to a wall using the wall bracket
(accessory).
3.1.2 Setting up the power supply unit
➜ Set up the power supply unit in accordance with the corresponding instructions.
3.1.3 Setting up the weighing platform
➜ Set up the analog weighing platform in accordance with the corresponding
operating and installation instructions.
Set up the system solution Analog Ex1 in accordance with the corresponding
installation instructions.10 Guide for installers 72203958C 11/12
InstallationIND226x3.1.4 Setting up the ACM200
➜ Set up the interface converter ACM200 in the safe area.
See dimensional drawing on Page 20 for drill hole dimensions for fixed
installation.
3.2 Connecting devices
CAUTION
• The clamping section of the earthing cable gland must agree with the outer
diameter of the weighing platform cable to be connected.
• Use the supplied flexible tubes to protect the individual wires of the weighing
platform cable on the inside of the IND226x.
Connect the devices in the following order:
1. Connect the weighing platform or system solution Analog Ex1 to the weighing
terminal IND226x.
2. If present, connect intrinsically safe equipment (e.g. a simple switch / push
button) to the intrinsically safe input of the weighing terminal IND226x.
3. Connect the power supply unit (APS500 / APS501, APS768x or External Battery
Pack) to the weighing terminal IND226x.
4. Connect the interface converter ACM200, if present, to the weighing terminal
IND226x.
5. Install the equipotential bonding, see Section 3.4.
6. Connect power supply, see Section 3.5.
3.2.1 Preparatory work
Connection of the devices is generally carried out with the accompanying standard
cables. Cables of other lengths can be used instead of the standard cables if they are
customized in accordance with Chapter 4. This applies for the following connections
• from the weighing platform or system solution Analog Ex1 to the weighing
terminal,
• from the power supply unit APS500 / APS501 or APS768x to the weighing
terminal,
• from the interface converter ACM200 to the weighing terminal.Guide for installers 72203958C 11/12 11
Installation IND226x3.2.2 General connection procedure
1. Open the device.
2. Pull the customized cable through the earthing cable gland. To do this
– dismantle the earthing cable gland or remove the blind plug,
– ensure the exact course of the cable and properly positioned seals,
– tighten the earthing cable gland.
3. Connect the cable in the device according to the terminal diagram.
4. For the power supply unit APS500 / APS501 connect the cable shield to the
terminal housing.
At an External NiMH battery pack check whether the cable shield is connected to
the "Ex-e" explosion-proof cable gland. If not, connect the cable shield to the
housing frame
5. Lay the cable in the cable holders on the inside of the housing.
6. Close device.
3.2.3 Installing/connecting the serial data interface
2
1
1. Secure the Interface IND or Interface Remote to the securing bolts with 3 stainless
steel screws (1).
2. Plug the included interface cable (2) into connector J2 on the serial data
interface and into connector J4 on the mainboard IND226x.
3. Connect the peripheral device to connector COM4 of the serial data interface
according to terminal diagram 72203677.12 Guide for installers 72203958C 11/12
InstallationIND226x3.2.4 Connection of the digital input at the IND226x
CAUTION
Design, calculation and installation of equipment at the digital input is solely the
responsibility of the owner, see section 3.3.
1. Connect only certified devices which are approved for Zone 1/21 or Division 1
hazardous areas.
When dimensioning the device to be connected, take the particularly low
current/voltage value of the active input of the IND226x into consideration.
2. Check the characteristic values for intrinsic safety in accordance with the
conformity certificate of the IND226x and the equipment to be connected
according to the conditions in Section 3.3. Document checking of the
characteristic values.
3. Customize a cable on the weighing terminal side in accordance with Section 4.3
and on the peripheral side according to the device to be connected. Heed the
maximum cable length here.
4. Connect the cable on the peripheral device side according to the intended device.
Ensure correct polarity here!
3.3 Selecting peripheral devices
CAUTION
Refer to the approval documentation of the peripheral device for all characteristic
values of the peripheral device listed in the following.
The following conditions must be fulfilled. See also terminal diagram IND226x:
1. Ui (peripheral device) ≥ U0 (IND226x)
2. Ii (peripheral device) ≥ I0 (IND226x)
3. Pi (peripheral device) ≥ P0 (IND226x)
4. Ci (peripheral device) + Ccable ≤ Co (IND226x)
5. Li (peripheral device) + Lcable ≤ Lo (IND226x)
6. La max (peripheral device) / Ra (peripheral device) < Lcable / Rcable,
with Lcable being the length-based inductivity and Rcable the length-specific
resistance of the cable to be used.
ATEX Directive for connection to the active input
In the case of a simple apparatus in accordance with Section 5.7 EN/IEC 60079-1,
the external simple apparatus in a hazardous gas environment does not require an
identification for use in Zone 1.
In a hazardous dust environment, Table 1 of the EN/IEC 61241-11 has to be taken
into consideration, for example the relevant regulation has to be applied for the
certified output P0 = 1.4 mW.Guide for installers 72203958C 11/12 13
Installation IND226xFM Directive for connection to the active input
A simple apparatus is defined in Section 504.2 of the National Electric Code
(NFPA 70) as "An electrical component or combination of components of simple
construction with well-defined electrical parameters that does not generate more than
1.5 volts, 100 milliamps, and 25 milliwatts, and is compatible with the intrinsic
safety of the circuit in which it is used."
Section 504.4 of the National Electric Code states that "simple apparatus, as
described on the control drawing, shall not be required to be listed".
3.4 Installing the equipotential bonding
Equipotential bonding must be installed by an electrician authorized by the owner.
METTLER TOLEDO Service only has a monitoring and consulting function here.
➜ Connect equipotential bonding (EB) of all devices (power supply unit, weighing
terminal, interface converter and weighing platform) in accordance with the
terminal diagram and the country-specific regulations and standards. In the
process it must be ensured that
– all device housings are connected to the same potential via the EB terminals,
– no circulating current flows via the cable shielding for intrinsically safe circuits,
– the neutral point for equipotential bonding is as close to the weighing system
as possible.
3.5 Connecting power supply
EXPLOSION HAZARD
The mains connection of the power supply unit must be made by a professional
electrician authorized by the owner and in accordance with the respective terminal
diagram, the accompanying installation instructions as well as the country-specific
regulations.14 Guide for installers 72203958C 11/12
Optional workIND226x4 Optional work
4.1 Customizing connection cables: Weighing platform / APS768x
Customer-specific cables for intrinsically safe circuits must be customized as follows:
Cable Dimension A (IND226x) Dimension B Max. length
IND226x – APS768x 4x2x0.5 mm2 + 1x0.5 mm2 215 mm 80 mm 50 m
IND226x – Weighing platform / system solution
Analog Ex1
3x2x0.75 mm21 215 mm 80 mm 122 m1
A B
Earthing cable gland
Cable shielding
Push sleeve over wires
and cable shielding
As per country-specific regulations for
intrinsically safe circuits
Wire end ferrules
with plastic collar,
crimp connection
1. Cut cable to length and strip cable ends according to dimension A/B.
2. Shorten cable shielding on both sides to 10 mm.
3. Strip wire ends.
4. Crimp wire end ferrules onto wire ends with a crimping tool.
5. Push second rear section of earthing cable gland onto cable.
6. Push sleeve over wires and cable shielding. Fold over cable shielding.
7. Push on front section of cable gland and screw onto rear section.Guide for installers 72203958C 11/12 15
Optional work IND226x4.2 Connection cable extension power supply unit
APS500 / APS501
The connection cable premounted at the power supply unit APS500 / APS501 cannot
be replaced. Therefore, a junction box is required in order to extend the connection
cable. This is available as an accessory (for the Order Number please refer to the
technical documentation of the power supply unit APS500 / APS501).
IND226x APS
500/501
3 m
max. 12 m
max. 15 m
A B
1
2 x 0.75 mm2
1 Junction box with junction PCB
4.2.1 Customizing cables
Customer-specific cables for intrinsically safe circuits must be customized as follows:
Cable Dimension A (IND226x)
Dimension B Max. length
IND226x – APS500/501 2x0.75 mm2 215 mm 80 mm 12 m
A B
Earthing cable gland
Cable shielding
Push sleeve over wires
and cable shielding
As per country-specific regulations for
intrinsically safe circuits
Wire end ferrules
with plastic collar,
crimp connection
1. Cut cable to length and strip cable ends according to dimension A/B.
2. Shorten cable shielding on both sides to 10 mm.
3. Strip wire ends.
4. Crimp wire end ferrules onto wire ends with a crimping tool.
5. Push second rear section of earthing cable gland onto cable.
6. Push sleeve over wires and cable shielding. Fold over cable shielding.
7. Push on front section of cable gland and screw onto rear section.16 Guide for installers 72203958C 11/12
Optional workIND226x4.2.2 Connecting
APS500 / APS501 –
junction box
1. Introduce the premounted Ex-i connection cable via a suitable and approved
earthing cable gland into the junction box.
2. Ensure correct positioning of the seal and tighten the earthing cable gland.
3. Connect the conductors of the premounted connection cable to the junction PCB
of the junction box.
Place cable shielding on the junction box housing.
See the documentation on APS500 / APS501 for the connection assignment.
Junction box – IND226x 1. Introduce the customized customer-specific Ex-i connection cable via the
supplied earthing cable gland into the junction box.
2. Ensure correct positioning of the seal and tighten the cable gland.
3. Connect the conductors of the customized connection cable to the junction PCB
of the junction box.
See the documentation on APS500 / APS501 for the connection assignment.
4. Introduce the customized customer-specific cable into the IND226x and connect
it in accordance with the terminal diagram 72203677 found on page 24.Guide for installers 72203958C 11/12 17
Optional work IND226x4.3 Customizing connection cables: Second display /
interface converter ACM200
Customer-specific cables for intrinsically safe circuits must be customized as follows:
Cable Dim. A IND226x (M) Dim. B
Max.
length
IND226x (Master) – IND226x
IND226x – ACM200 2x2x0.5 mm
2 50 mm 50 mm 300 m
BA
Earthing cable gland
Cable shielding
Push sleeve over wires
and cable shielding
As per country-specific
regulations for
intrinsically safe circuits
Wire end ferrules
with plastic collar,
crimp connection
1. Cut cable to length and strip cable ends according to dimension A/B.
2. Shorten cable shielding on both sides to 10 mm.
3. Strip wire ends.
4. Crimp wire end ferrules onto wire ends with a crimping tool.
5. Push second rear section of earthing cable gland onto cable.
6. Apply the cable shielding only on the IND226x (Master) end.
To do so, push the sleeve over the wires and cable shielding and fold over the
cable shielding.
7. Push on front section of cable gland and screw onto rear section.18 Guide for installers 72203958C 11/12
Optional workIND226x4.4 Configuring module ACM200-CL/RS422
4.4.1 Opening the housing
1. Pull the power plug.
2. Open the housing cover of the ACM200.
4.4.2 Setting the jumpers
➜ Plug in the jumpers W1 to W5 as per the table below.
Jumper Meaning Factory setting Note
W2 CL20mA interface Plugged in
The transmission and reception
loop operating mode can also
be selected, see 4.4.3
W3 RS422 interface – A matching resistor W1 can
also be setW4 RS485 interface –
W1 Matching resistor
Open, no
matching resistor
Only for RS422/RS485, the
matching resistor is required
only on the last component of a
field bus
W5 Power supply "12 V" position
With the used wide-range power
supply unit, it is necessary to
insert the jumper in the "12 V"
position
4.4.3 Selecting the CL interface operating mode for the module ACM200-CL/RS422
The CL interface of the optional module ACM200-CL/RS422 can be operated with
either an active or passive transmission and reception loop.
Factory setting: Passive transmission and reception loop
1. Pull the power plug.
2. Open the housing cover of the ACM200.
3.
ON DIP
K1
1 2 3 4 5 6
Set the desired operating mode with the dip switch K1 on the module ACM200CL/RS422.
Operating mode K1 K2 K3 K4 K5 K6
TXD passive, RXD passive
(factory setting)
on on off off off off
TXD active, RXD active off off on on on on
TXD passive, RXD active off on on on off off
TXD active, RXD passive on off off off on on
4.4.4 Closing the housing
➜ Close the housing cover. Ensure correct position of the seal when doing so.Guide for installers 72203958C 11/12 19
Technical data IND226x5 Technical data
5.1 Dimensional drawing
90
66
132
148
150
220
M5
Under O K O ver PT
Ne t lb k g
MinW eigh
Dimensions in mm
IND226x
81
R5
200
175160
69.5
R3.5
Dimensions in mm
ACM20020 Guide for installers 72203958C 11/12
Technical dataIND226x5.2 Technical data of the CL20mA interface of the module
ACM200-CL/RS422
Type of interface • 20 mA current loop, 2 transmission loops
• Active or passive operation
• Signal level 0: 20 mA
• Signal level 1: 0 mA
• Electrical isolation only in passive configuration and up to
U = 30 VAC, Û = 42 V, U = 60 VDC
Interface parameters Operating mode Full duplex
Transmission type Bit serial, asynchronous
Transmission code ASCII
Data bits 7/8
Parity Even, odd, zero, one, none
Baud rate 150, 300, 600, 1200, 2400, 4800, 9600, 19200
Transmission and/or
reception loop
passive
One external power source supplies the transmission and/or reception loop
Imax 30 mA
Umax 27 V
Voltage range 15 V (+10 % / –0 %)
Current level 18 mA – 24 mA (high level)
Edge steepness 2 – 20 mA/μs
To set operating mode, see Section 4.4.2
Transmission and/or
reception loop
active
One internal power source supplies the transmission and/or reception loop
Voltage 12 VDC
Current Adjusted to ±2 mA, for transmission and/or reception
loop
To set operating mode, see Section 4.4.2
Cable • Shielded, twisted pair
• Line resistance ≤ 125 Ω/km
• Line cross-section ≥ 0.14 mm2
• Line capacity ≤ 130 nF/km
• Max. 1000 m for baud rates up to 4800 baud
• Max. 600 m for 9600 baud
• Max. 300 m for 19200 baudGuide for installers 72203958C 11/12 21
Disposal IND226x6 Disposal
In conformance with the European Directive 2002/96/EC on Waste Electrical and
Electronic Equipment (WEEE), this device may not be disposed of in domestic waste.
This also applies to countries outside the EU as per their specific regulations.
➜ Please dispose of this product in accordance with local regulations at the
collecting point specified for electrical and electronic equipment.
If you have any questions, please contact the responsible authority or the distributor
from which you purchased this device.
Should this device be passed on to other parties (for private or professional use), the
content of this regulation must also be related.
Thank you for your contribution to environmental protection.22 Guide for installers 72203958C 11/12
DisposalIND226xGuide for installers 72203958C 11/12 23
Terminal diagram IND226x7
bl ue : N
br ow n: P
ye l/g
rn : E
/G
H
az ar d o u s ar ea S
af e ar ea ac tiv
e in tr in si ca lly
sa fe 3
U
2
4
br ow n U
3
5
ro se 6
gr ey 7
bl ac k 8
re d gr ee n 9
bl ue 2
ye llo
w G
N
D
1
w hi te U
1
P
G
N
D
G
N
D
G
N
D
G
N
DU
4
U
5
U
6
N
C
1)
m ax . 5
0
m 5)
P
A
al te rn at iv e B
at te ry P
ac k al te rn at iv e blue
w hi te A
P
S
50
. a
ct iv e in tr in si ca lly
s af e br ow n: P
bl ue : N
ye l/g
rn : E
/G
P
ow er su pp ly6)
P.
b ro w n N
. b
lu e E
/G
. y
el /g rn P
ow er su pp ly 6)
pa ss iv e in tr in si ca lly
s af e M
ai n b o ar d IN
D
22
6x 5)
P
A
max. 15 m
3) 7)
3
)
7)
m ax . 3
m max. 122 m 2)
7)
1
2
3
4
5
6
7
B
5)
P
A
5)
P
A
Exc+
Sen+
Sig+
Sig–
Sen–
Exc–
5)
P
A
1 2I
+
G
N
D
7)
8)
5)
9
)
P
A
ac tiv
e in tr in si ca lly
sa fe E
xt er na l pu sh bu tto
n 8)
8)
3
In te rf ac e IN
D
J4
J2
4
ac tiv
e in tr in si ca lly
s af e 2 1
C
O
M
4
34 2 1
or an ge re d ye llo
w bu e 4)
7
)
m ax . 3
00
m pa ss iv e in tr in si ca lly
s af e 5)
11
)
PA
+
+
or an ge re d ye llo
w bb lu e M
ai n b o ar d A
C
M
20
0
C
O
M
R
xD G
N
D
T
xD R
S
23
2
D
C
IN
S
hi el d bl ac k w hi te re d +–
A
C
M
20
0
+

ac tiv
e in tr in si ca lly
s af e 1
2
3
4
5
6
7
B
A
B
A
P
S
76
8x P
S
U
x B
R
S
23
2
10
m 9p in S
ub D
6)
P
ow er s up pl y 12
)
P
ow er su pp ly ac tiv
e in tr in si ca lly
s af e ac tiv
e in tr in si ca lly
s af e bl ue white
Ju nc tio
n pr in t o
r st ra in ga ug e ce ll co nn ec tio
n ca bl e of th e an al og w ei gh in g pl at fo rm 8)
D
et ai l: W
ith
s tr ai n ga ug e w ei gh in g ce lls
w ith
4
co nd uc to rs m er ge te rm in al s 1-
2
an d 6-
7!
W
id e ra n g e p o w er s u p p ly u n it

Terminal diagram24 Guide for installers 72203958C 11/12
IND226x – Intrinsically safe entity parameters
Scale interface U0 (Voc) I0 (Isc) P0 C0 (Ca) L0 (La)
CENELEC approval CFMUS approval
Cables conforming to EN50039 and EN60079-14 For installation please refer to ANSI/ISA RP 12.06.01, "Installarinsically safe devices in Class I hazardous areas"
per country-specific regulations for intrinsically safe
1 x 0.02 in2) shielded and twisted pair
wisted pair
air
cable shield only applied to IND226x end
ction of the equipotential bonding (EB) as per
FPA 70, Article 504 and ANSI/IA RP 12.06.01 or
ian Electrical Code C22.2. It must be ensured that the
ngs of all devices are connected to the same potential
e EB terminals. No circulating current may flow via the
ing of the intrinsically safe cables.
ations;
protect it against damage.
ng conditions:
Pi ≥ Po
cordance with NEC (NFPA 70),
m = 250 V rms or DC.
ross section: min. 0.2 mm2, max. 0.8 mm2
APS768x, see terminal diagram 22006397
ice variant ACM200-DC
F)
me Scale Designation
hultz
Terminal diagram
IND226x
hultz
Code
72203677
Term
inal diagram
G
uide for installers 72203958C 11/12
25
IN
D
226x
aACM200 – Intrinsically safe entity parameters
Weighing platform characteristics
Measuring cells max. 4
Weighing platform impedance ≥ 87 Ω
Nominal characteristic load cell 2 mV/V or 3 mV/V
Terminals B 1–7 5.88 V 156 mA 0.92 W 200 nF 0.3 mH
Digital input (active) U0 (Voc) I0 (Isc) P0 C0 (Ca) L0 (La)
Terminals I 1–2 5.4 V 1 mA 1.4 mW 100 nF 0.1 mH
Power supply Ui Ii Pi Ci Li
Terminals P 1–9 13 V
3.16 A 12 W
0 nF 0 mH
limited internally
Interface IND U0 (Voc) I0 (Isc) P0 C0 (Ca) L0 (La)
COM4, Terminals 1–4 5.88 V 144 mA 212 mW 600 nF 0.4 mH
Interface Remote Ui Ii Pi Ci Li
COM4, Terminals 1–4 10 V 300 mA 500 mW 120 nF 0 mH
Passive interface Ui Ii Pi Ci Li
COM, Terminals 1–4 10 V 300 mA 500 mW 120 nF 0 mH
Color codes RWMxPFA579x
PFA575x
PFA459x
PUA579x
DB...sTx
DCS...sTx PBA430x
Exc+ gray gray blue green
Sen+ yellow yellow green blue
Sig+ white white white white
Sig– brown brown red red
Sen– green green gray brown
Exc– pink pink black black
for intrinsically safe circuits tion of int
Cable as
circuits
• Cable inlet via earthing cable gland
• Cable as per installation instructions ME-72203959
1) Cable 4 x 2 x 0.5 mm2 + 1 x 0.5 mm2 (4 x 2 x 0.02 in2 +
2) Cable 3 x 2 x 0.75 mm2 (3 x 2 x 0.03 in2) shielded and t
3) Cable 2 x 0.75 mm2 (2 x 0.03 in2) shielded and twisted p
4) Cable 2 x 2 x 0.5 mm2 (2 x 2 x 0.02 in2) twisted pair and
5) Connection of equipotential bonding (EB) as per
country-specific regulations.
It must be ensured that the housings of all
devices are connected to the same potential via
the EB terminals. No circulating current may flow
via the shielding of the intrinsically safe cables.
5) Conne
ANSI/N
Canad
housi
via th
shield
6) Mains connection in accordance with country-specific regul
for supply voltage and frequency refer to rating plate
7) Lay cabling securely so that it does not move and effectively
8) ATEX- and FM-approved devices in accordance with followi
Ui ≥ Uo (Voc) Ii ≥ Io (Isc)
Ci + Ccable < Co (Ca) Li + Lcable < Lo (La)
Active input: Connection of simple electrical apparatus in ac
Sections 504.2 and 504.4
9) For connecting devices with a maximum effective value of U
10)Use only shielded cable. Max. cable length 304 m. Cable c
11)Can also be used in conjunction with the power supply unit
12)A power supply with 24 V DC is possible in the case of dev
Ambient temperature range: –10 °C to +40 °C (14 °F to 104 °
C 11/12 Schultz
B 11/03 Schultz
A 09/07 Schultz Date Na
Edition
Change Date Name
Proc. by 05/07 Sc
Checked 05/07 Sc
Replacement for:
/
Sheet 1/3
Mettler-Toledo (Changzhou) Measurement Technology Ltd.
Terminal diagram IND226xD
C
IN
S
hi el d +

bl ue : N
br ow n: P
ye l/g
rn : E
/G
H
az ar d o u s ar ea S
af e ar ea ac tiv
e in tr in si ca lly
sa fe 3
U
2
4
br ow n U
3
5
ro se 6
gr ey 7
bl ac k 8
re d gr ee n 9
bl ue 2
ye llo
w G
N
D
1
w hi te U
1
P
G
N
D
G
N
D
G
N
D
G
N
DU
4
U
5
U
6
N
C
1)
m ax . 5
0
m 5)
P
A
al te rn at iv e B
at te ry P
ac k al te rn at iv e blue
white
bl ue w hi te A
P
S
50
. a
ct iv e in tr in si ca lly
s af e br ow n: P
bl ue : N
ye l/g
rn : E
/G
P
ow er su pp ly6)
P.
b ro w n N
. b
lu e E
/G
. y
el /g rn ow er pp ly in tr in si ca lly
s af e M
ai n b o ar d IN
D
22
6x 5)
P
A
8)
max. 15 m
3) 7)
3
)
7)
m ax . 3
m max. 122 m 2)
7)
1
2
3
4
5
6
7
B
5)
P
A
5)
P
A
Exc+
Sen+
Sig+
Sig–
Sen–
Exc–
5)
P
A
1 2I
+
G
N
D
7)
8)
5)
9
)
P
A
ac tiv
e in tr in si ca lly
s af e E
xt er na l pu sh bu tto
n 8)
8)
3
In te rf ac e IN
D
J4
J2
4
ac tiv
e in tr in si ca lly
s af e 2 1
C
O
M
4
34 2 1
or an ge re d ye llo
w bl ue 4)
7
)
m ax . 3
00
m pa ss iv e in tr in si ca lly
s af e 5)
11
)
10
)
12
)
PA
+
+
or an ge ye llo
w gr ee n w hi te br ow n re d ye llo
w bl ue M
ai n b o ar d A
R
S
42
2/
48
5
C
M
20
0
C
O
M
R
xD G
N
D
T
xD G
N
D
R
S
23
2
C
L
20
m A
+–
W
id e ra n g e p o w er s u p p ly u n it A
C
M
20
0
W
4
W
3
W
2
W
1
R
S
48
5
R
S
42
2
C
L2
0m A
ON
K1
DIP
1 6
ac tiv
e nt rin
si ca lly
s af e 1
2
3
4
5
6
7
B
A
B
A
P
S
76
8x P
S
U
x B
C
+24V +12V
T
x+ (
A
)
al te rn at iv e R
S
42
2(
48
5)
P
ow er su pp ly 6)
P
ow er s up pl y al te rn at iv e C
L/
ID
N
et 10
m T
x– (
B
)
R
x+ R
x– R
x– R
x+ T
x– T
x+ G
N
D
W5
S
hi el d DC IN– +
A
C
M
20
0-
C
L
/R
S
42
2/
48
5
ac tiv
e in tr in si ca lly
s af e ac tiv
e in tr in si ca lly
s af e et ai l: W
ith
s tr ai n ga ug e w ei gh in g ce lls
w ith
co nd uc to rs m er ge te rm in al s 1-
2
an d 6-
7!
Ju nc tio
n pr in t o
r st ra in ga ug e ce ll co nn ec tio
n ca bl e of th e an al og w ei gh in g pl at fo rm

26 Guide for installers 72203958C 11/12
IND226x – Intrinsically safe entity parameters
Scale interface U0 (Voc) I0 (Isc) P0 C0 (Ca) L0 (La)
CENELEC approval CFMUS approval
Cables conforming to EN50039 and EN60079-14 For installation please refer to ANSI/ISA RP 12.06.01, "Installarinsically safe devices in Class I hazardous areas"
per country-specific regulations for intrinsically safe
1 x 0.02 in2) shielded and twisted pair
wisted pair
air
cable shield only applied to IND226x end
ction of the equipotential bonding (EB) as per
FPA 70, Article 504 and ANSI/IA RP 12.06.01 or
ian Electrical Code C22.2. It must be ensured that the
ngs of all devices are connected to the same potential
e EB terminals. No circulating current may flow via the
ing of the intrinsically safe cables.
ations;
protect it against damage.
ng conditions:
Pi ≥ Po
cordance with NEC (NFPA 70),
m = 250 V rms or DC.
ross section: min. 0.2 mm2, max. 0.8 mm2
APS768x, see terminal diagram 22006397
ice variant ACM200-DC
F)
me Scale Designation
hultz
Terminal diagram
IND226x
hultz
Code
72203677
Term
inal diagram
G
uide for installers 72203958C 11/12
27
IN
D
226x
aACM200 – Intrinsically safe entity parameters
Weighing platform characteristics
Measuring cells max. 4
Weighing platform impedance ≥ 87 Ω
Nominal characteristic load cell 2 mV/V or 3 mV/V
Terminals B 1–7 5.88 V 156 mA 0.92 W 200 nF 0.3 mH
Digital input (active) U0 (Voc) I0 (Isc) P0 C0 (Ca) L0 (La)
Terminals I 1–2 5.4 V 1 mA 1.4 mW 100 nF 0.1 mH
Power supply Ui Ii Pi Ci Li
Terminals P 1–9 13 V
3.16 A 12 W
0 nF 0 mH
limited internally
Interface IND U0 (Voc) I0 (Isc) P0 C0 (Ca) L0 (La)
COM4, Terminals 1–4 5.88 V 144 mA 212 mW 600 nF 0.4 mH
Interface Remote Ui Ii Pi Ci Li
COM4, Terminals 1–4 10 V 300 mA 500 mW 120 nF 0 mH
Passive interface Ui Ii Pi Ci Li
COM, Terminals 1–4 10 V 300 mA 500 mW 120 nF 0 mH
Color codes RWMxPFA579x
PFA575x
PFA459x
PUA579x
DB...sTx
DCS...sTx PBA430x
Exc+ gray gray blue green
Sen+ yellow yellow green blue
Sig+ white white white white
Sig– brown brown red red
Sen– green green gray brown
Exc– pink pink black black
for intrinsically safe circuits tion of int
Cable as
circuits
• Cable inlet via earthing cable gland
• Cable as per installation instructions ME-72203959
1) Cable 4 x 2 x 0.5 mm2 + 1 x 0.5 mm2 (4 x 2 x 0.02 in2 +
2) Cable 3 x 2 x 0.75 mm2 (3 x 2 x 0.03 in2) shielded and t
3) Cable 2 x 0.75 mm2 (2 x 0.03 in2) shielded and twisted p
4) Cable 2 x 2 x 0.5 mm2 (2 x 2 x 0.02 in2) twisted pair and
5) Connection of equipotential bonding (EB) as per
country-specific regulations.
It must be ensured that the housings of all
devices are connected to the same potential via
the EB terminals. No circulating current may flow
via the shielding of the intrinsically safe cables.
5) Conne
ANSI/N
Canad
housi
via th
shield
6) Mains connection in accordance with country-specific regul
for supply voltage and frequency refer to rating plate
7) Lay cabling securely so that it does not move and effectively
8) ATEX- and FM-approved devices in accordance with followi
Ui ≥ Uo (Voc) Ii ≥ Io (Isc)
Ci + Ccable < Co (Ca) Li + Lcable < Lo (La)
Active input: Connection of simple electrical apparatus in ac
Sections 504.2 and 504.4
9) For connecting devices with a maximum effective value of U
10)Use only shielded cable. Max. cable length 304 m. Cable c
11)Can also be used in conjunction with the power supply unit
12)A power supply with 24 V DC is possible in the case of dev
Ambient temperature range: –10 °C to +40 °C (14 °F to 104 °
C 11/12 Schultz
B 11/03 Schultz
A 09/07 Schultz Date Na
Edition
Change Date Name
Proc. by 05/07 Sc
Checked 05/07 Sc
Replacement for:
/
Sheet 2/3
Mettler-Toledo (Changzhou) Measurement Technology Ltd.
ga ug e ce ll co nn ec tio
n ca bl e of th e an lo g w ei gh in g pl at fo rm 8)
Terminal diagram IND226xH
az ar do us a re a S
af e ar ea ac tiv
e in tr in si ca lly
sa fe3
U
2
4
br ow n U
3
5
pi nk 6
gr ay 7
bl ac k 8
re d gr ee n 9
bl ue 2
ye llo
w G
N
D
1
w hi te U
1
P
G
N
D
G
N
D
G
N
D
G
N
DU
4
U
5
U
6
N
C
1)
m ax . 5
0
m 5)
E
B
al te rn at iv e A
P
S
76
8x P
S
U
x B
at te ry P
ac k al te rn at iv e blue
white
bl ue w hi te A
P
S
50
.
br ow n: P
bl ue : N
ye /g re en : E
/G
P
ow er su pp ly6)
P.
b ro w n N
. b
lu e E
/G
. y
e/ gr ee n P
ow er su pp ly 6)
pa ss iv e in tr.
s af e M
ai nb oa rd IN
D
22
6x 5)
E
B
Ju nc tio
n pr in t o
r st ra ina
ct iv e in tr in si ca lly
s af e max. 15 m
3) 7)
3
)
7)
m ax . 3
m max. 122 m 2)
7)
1
2
3
4
5
6
7
B
+
5)
E
B
5)
E
B
Exc+
Sen+
Sig+
Sig
Sen
Exc
5)
E
B
1 2I
7)
ac tiv
e in tr in si ca lly
s af e ac tiv
e in tr in si ca lly
s af e 8)
8)
3
In te rf ac e IN
D
J4
J2
4
ac tiv
e in tr in si ca lly
s af e2 1
C
O
M
4
or an ge re d ye llo
w bl ue +
4) m
ax . 3
00
m ac tiv
e in tr in si ca lly
s af e B
B
a28 Guide for installers 72203958C 11/12
Terminal diagramIND226x
IN
D2
26
x Re pl ac em en t f
or :
/
Sh ee t 3
/3
M
et tle
rTo le do (
Ch an gz ho u) M
ea su re m en t T
ec hn ol og y Lt d. Co de 7
22
03
67
7
a 3
U
2
4
br ow n U
3
5
pi nk 6
gr ay 7
bl ac k 8
re d gr ee n 9
bl ue 2
ye lll
ow G
N
D
1
w hi te U
1
P
G
N
D
G
N
D
G
N
D
G
N
DU
4
U
5
U
6
N
C
1)
m ax . 5
0
m 5)
E
B
al te rn at iv e A
P
S
76
8x B
at te ry P
ac k al te rn at iv e blue
white
bl ue w hi te A
P
S
50
.
ac tiv
e in tr in si ca lly
s af e br ow n: P
bl ue : N
ye /g re en : E
/G
P
ow er su pp ly6)
P.
b ro w n N
. b
lu e E
/G
. y
e/ gr ee n P
ow er su pp ly 6)
pa ss iv e in tr.
s af e M
ai n b o ar d IN
D
22
6x 5)
E
B
max. 15 m
3) 7)
3
)
7)
m ax . 3
m 1
2
3
4
5
6
7
B
+
5)
E
B
5)
E
B
1 2I
7)
ac tiv
e in tr in si ca lly
s af e ac tiv
e in tr in si ca lly
s af e 8)
8)
3
In te rf ac e R
em o te J4
J2
4
pa ss iv e in tr in si ca lly
s af e 2 1
C
O
M
4
or an ge re d ye llo
w bl ue +
B
C
11
/1
2
Sc hu ltz
B
11
/0
3
Sc hu ltz
A
09
/0
7
Sc hu ltz
D
at e N
am e Sc al e D
es ig na tio
n Ed itio
n Ch an ge D
at e N
am e Pr oc . b
y 05
/0
7
Sc hu ltz
Te rm in al d ia gr am Ch ec ke d 05
/0
7
Sc hu ltz
aGuide for installers 72203958C 11/12 29
Congratulations on choosing the quality and precision of METTLER TOLEDO. Proper use according to these instructions and regular calibration and maintenance by our factory-trained service team ensure dependable and accurate
operation, protecting your investment. Contact us about a ServiceXXL agreement tailored to your needs and budget.
We invite you to register your product at www.mt.com/productregistration so we can contact you about enhancements, updates and important notifications concerning your product.
*72203958C*
72203958C
Subject to technical changes © Mettler-Toledo (Changzhou) Ltd. 11/12 Printed in Germany 72203958C
Mettler-Toledo (Changzhou) Measurement Technology Ltd.
10 Kunlun Road, Changzhou Xinbei District, Jiangsu Province, P.R. China 213125
Tel. 0086-519-664-2040
Fax 0086-519-664-1991
Internet http://www.mt.com

PDF Document reader online

This website is focused on providing document in readable format, online without need to install any type of software on your computer. If you are using thin client, or are not allowed to install document reader of particular type, this application may come in hand for you. Simply upload your document, and Docureader.top will transform it into readable format in a few seconds. Why choose Docureader.top?

  1. Unlimited sharing - you can upload document of any size. If we are able to convert it into readable format, you have it here - saved for later or immediate reading
  2. Cross-platform - no compromised when reading your document. We support most of modern browers without the need of installing any of external plugins. If your device can oper a browser - then you can read any document on it
  3. Simple uploading - no need to register. Just enter your email, title of document and select the file, we do the rest. Once the document is ready for you, you will receive automatic email from us.

Previous 10

Next 10